**Why is POWEReasy showing a warning?**

Your site has observed an unbalanced current in the electrical system. IEEE1159 recommends unbalanced currents to be measured within a maximum value of 30%. POWEReasy measures this over a 24 hour period and determines the average unbalance across the entire electrical system connected to the device.

 

**When do you need to fix this and why?**

Unbalanced currents are not safe for your electrical system. It leads to excessive current flow in the neutral conductors and overburdening one phase over another. This has an impact on the efficiency of the entire electrical system. The increased current in neutral can further lead to overheating of the neutral conductor and eventually a neutral fault condition. Having the unbalanced currents fixed at your next weekly shutdown is advisable.

 

 Tags: [Unbalanced Currents Warnings Corrective Plan](https://blog.powereasy.in/topic/unbalanced-currents-warnings-corrective-plan)

#### Written by [Ganesh Karbele](https://blog.powereasy.in/author/ganesh-karbele)

### Subscribe to Email Updates

- [Recent](https://blog.powereasy.in/unbalanced-currents-warnings-corrective-plan#tab-1)
- [Popular](https://blog.powereasy.in/unbalanced-currents-warnings-corrective-plan#tab-2)
- [Categories](https://blog.powereasy.in/unbalanced-currents-warnings-corrective-plan#tab-3)

### Lists by Topic

- [Enhancing stability of electrical systems (3)](https://blog.powereasy.in/tag/enhancing-stability-of-electrical-systems)
- [Improving safety with automation (3)](https://blog.powereasy.in/tag/improving-safety-with-automation)
- [Automating essential services (2)](https://blog.powereasy.in/tag/automating-essential-services)
- [Critical Overvoltage Fault Corrective Plan (2)](https://blog.powereasy.in/tag/critical-overvoltage-fault-corrective-plan)
- [Critical Voltage Harmonics Fault Corrective Plan (2)](https://blog.powereasy.in/tag/critical-voltage-harmonics-fault-corrective-plan)
- [Identifying & Correcting Electrical Warnings (2)](https://blog.powereasy.in/tag/identifying-correcting-electrical-warnings)
- [Adopting smart electricity sustainability (1)](https://blog.powereasy.in/tag/adopting-smart-electricity-sustainability)
- [Arcing Faults Corrective Plan (1)](https://blog.powereasy.in/tag/arcing-faults-corrective-plan)
- [CIRCUIT BREAKERS: IS THAT ALL YOU GOT? (1)](https://blog.powereasy.in/tag/circuit-breakers-is-that-all-you-got)
- [Critical Earth Leakage Fault Corrective Plan (1)](https://blog.powereasy.in/tag/critical-earth-leakage-fault-corrective-plan)
- [Critical Earth Voltage Fault Corrective Plan (1)](https://blog.powereasy.in/tag/critical-earth-voltage-fault-corrective-plan)
- [Critical Undervoltage Fault Corrective Plan (1)](https://blog.powereasy.in/tag/critical-undervoltage-fault-corrective-plan)
- [Does stabilizer reduce electricity bill? (1)](https://blog.powereasy.in/tag/does-stabilizer-reduce-electricity-bill)
- [Earth Leakage Warnings Corrective Plan (1)](https://blog.powereasy.in/tag/earth-leakage-warnings-corrective-plan)
- [Earth Voltage Warnings Corrective Plan (1)](https://blog.powereasy.in/tag/earth-voltage-warnings-corrective-plan)
- [Electrical fire risks (1)](https://blog.powereasy.in/tag/electrical-fire-risks)
- [GREEN, GREEN, FAIRY QUEEN (1)](https://blog.powereasy.in/tag/green-green-fairy-queen)
- [HEATING OF BASIC ELECTRONIC EQUIPMENT (1)](https://blog.powereasy.in/tag/heating-of-basic-electronic-equipment)
- [ICE BOX BABY AND OTHER JUGAADS (1)](https://blog.powereasy.in/tag/ice-box-baby-and-other-jugaads)
- [INDIA: MAKE IT OR BREAK IT (1)](https://blog.powereasy.in/tag/india-make-it-or-break-it)
- [Identifying & Correcting Electrical Faults (1)](https://blog.powereasy.in/tag/identifying-correcting-electrical-faults)
- [Inrush Current Warning Corrective Plan (1)](https://blog.powereasy.in/tag/inrush-current-warning-corrective-plan)
- [Loose Connections Warnings Corrective Plan (1)](https://blog.powereasy.in/tag/loose-connections-warnings-corrective-plan)
- [Neutral Loss Fault Correction Plan (1)](https://blog.powereasy.in/tag/neutral-loss-fault-correction-plan)
- [Overload Warnings Corrective (1)](https://blog.powereasy.in/tag/overload-warnings-corrective)
- [Overvoltage Warning Corrective Plan (1)](https://blog.powereasy.in/tag/overvoltage-warning-corrective-plan)
- [Phase Loss Fault Correction Plan (1)](https://blog.powereasy.in/tag/phase-loss-fault-correction-plan)
- [Phase Reversal Fault Correction Plan (1)](https://blog.powereasy.in/tag/phase-reversal-fault-correction-plan)
- [Power factor Warnings Corrective Plan (1)](https://blog.powereasy.in/tag/power-factor-warnings-corrective-plan)
- [Reverse Current Warnings Corrective Plan (1)](https://blog.powereasy.in/tag/reverse-current-warnings-corrective-plan)
- [Short Term Warning Corrective Plan (1)](https://blog.powereasy.in/tag/short-term-warning-corrective-plan)
- [Shortcircuit / Overload Fault Corrective Plan (1)](https://blog.powereasy.in/tag/shortcircuit-overload-fault-corrective-plan)
- [Simplify adoption of smart electricity (1)](https://blog.powereasy.in/tag/simplify-adoption-of-smart-electricity)
- [THE PRICE OF PROTECTION (1)](https://blog.powereasy.in/tag/the-price-of-protection)
- [The different type of Voltage Stabilizers? (1)](https://blog.powereasy.in/tag/the-different-type-of-voltage-stabilizers)
- [Time to replace your servo voltage stabilizer (1)](https://blog.powereasy.in/tag/time-to-replace-your-servo-voltage-stabilizer)
- [Unbalanced Currents Warnings Corrective Plan (1)](https://blog.powereasy.in/tag/unbalanced-currents-warnings-corrective-plan)
- [Under Voltage Warning Corrective Plan (1)](https://blog.powereasy.in/tag/under-voltage-warning-corrective-plan)
- [Voltage Harmonics Warning Corrective Plan (1)](https://blog.powereasy.in/tag/voltage-harmonics-warning-corrective-plan)
- [Voltage Surge Fault Corrective Plan (1)](https://blog.powereasy.in/tag/voltage-surge-fault-corrective-plan)
- [Voltage Unbalance Warning Corrective Plan (1)](https://blog.powereasy.in/tag/voltage-unbalance-warning-corrective-plan)
- [Voltage Variation Warning Corrective Plan (1)](https://blog.powereasy.in/tag/voltage-variation-warning-corrective-plan)
- [WHILE YOU WERE SLEEPING (1)](https://blog.powereasy.in/tag/while-you-were-sleeping)
- [What is Smart Electricity (1)](https://blog.powereasy.in/tag/what-is-smart-electricity)

see all

### Posts by Topic

- [Enhancing stability of electrical systems (3)](https://blog.powereasy.in/tag/enhancing-stability-of-electrical-systems)
- [Improving safety with automation (3)](https://blog.powereasy.in/tag/improving-safety-with-automation)
- [Automating essential services (2)](https://blog.powereasy.in/tag/automating-essential-services)
- [Critical Overvoltage Fault Corrective Plan (2)](https://blog.powereasy.in/tag/critical-overvoltage-fault-corrective-plan)
- [Critical Voltage Harmonics Fault Corrective Plan (2)](https://blog.powereasy.in/tag/critical-voltage-harmonics-fault-corrective-plan)
- [Identifying & Correcting Electrical Warnings (2)](https://blog.powereasy.in/tag/identifying-correcting-electrical-warnings)
- [Adopting smart electricity sustainability (1)](https://blog.powereasy.in/tag/adopting-smart-electricity-sustainability)
- [Arcing Faults Corrective Plan (1)](https://blog.powereasy.in/tag/arcing-faults-corrective-plan)
- [CIRCUIT BREAKERS: IS THAT ALL YOU GOT? (1)](https://blog.powereasy.in/tag/circuit-breakers-is-that-all-you-got)
- [Critical Earth Leakage Fault Corrective Plan (1)](https://blog.powereasy.in/tag/critical-earth-leakage-fault-corrective-plan)
- [Critical Earth Voltage Fault Corrective Plan (1)](https://blog.powereasy.in/tag/critical-earth-voltage-fault-corrective-plan)
- [Critical Undervoltage Fault Corrective Plan (1)](https://blog.powereasy.in/tag/critical-undervoltage-fault-corrective-plan)
- [Does stabilizer reduce electricity bill? (1)](https://blog.powereasy.in/tag/does-stabilizer-reduce-electricity-bill)
- [Earth Leakage Warnings Corrective Plan (1)](https://blog.powereasy.in/tag/earth-leakage-warnings-corrective-plan)
- [Earth Voltage Warnings Corrective Plan (1)](https://blog.powereasy.in/tag/earth-voltage-warnings-corrective-plan)
- [Electrical fire risks (1)](https://blog.powereasy.in/tag/electrical-fire-risks)
- [GREEN, GREEN, FAIRY QUEEN (1)](https://blog.powereasy.in/tag/green-green-fairy-queen)
- [HEATING OF BASIC ELECTRONIC EQUIPMENT (1)](https://blog.powereasy.in/tag/heating-of-basic-electronic-equipment)
- [ICE BOX BABY AND OTHER JUGAADS (1)](https://blog.powereasy.in/tag/ice-box-baby-and-other-jugaads)
- [INDIA: MAKE IT OR BREAK IT (1)](https://blog.powereasy.in/tag/india-make-it-or-break-it)
- [Identifying & Correcting Electrical Faults (1)](https://blog.powereasy.in/tag/identifying-correcting-electrical-faults)
- [Inrush Current Warning Corrective Plan (1)](https://blog.powereasy.in/tag/inrush-current-warning-corrective-plan)
- [Loose Connections Warnings Corrective Plan (1)](https://blog.powereasy.in/tag/loose-connections-warnings-corrective-plan)
- [Neutral Loss Fault Correction Plan (1)](https://blog.powereasy.in/tag/neutral-loss-fault-correction-plan)
- [Overload Warnings Corrective (1)](https://blog.powereasy.in/tag/overload-warnings-corrective)
- [Overvoltage Warning Corrective Plan (1)](https://blog.powereasy.in/tag/overvoltage-warning-corrective-plan)
- [Phase Loss Fault Correction Plan (1)](https://blog.powereasy.in/tag/phase-loss-fault-correction-plan)
- [Phase Reversal Fault Correction Plan (1)](https://blog.powereasy.in/tag/phase-reversal-fault-correction-plan)
- [Power factor Warnings Corrective Plan (1)](https://blog.powereasy.in/tag/power-factor-warnings-corrective-plan)
- [Reverse Current Warnings Corrective Plan (1)](https://blog.powereasy.in/tag/reverse-current-warnings-corrective-plan)
- [Short Term Warning Corrective Plan (1)](https://blog.powereasy.in/tag/short-term-warning-corrective-plan)
- [Shortcircuit / Overload Fault Corrective Plan (1)](https://blog.powereasy.in/tag/shortcircuit-overload-fault-corrective-plan)
- [Simplify adoption of smart electricity (1)](https://blog.powereasy.in/tag/simplify-adoption-of-smart-electricity)
- [THE PRICE OF PROTECTION (1)](https://blog.powereasy.in/tag/the-price-of-protection)
- [The different type of Voltage Stabilizers? (1)](https://blog.powereasy.in/tag/the-different-type-of-voltage-stabilizers)
- [Time to replace your servo voltage stabilizer (1)](https://blog.powereasy.in/tag/time-to-replace-your-servo-voltage-stabilizer)
- [Unbalanced Currents Warnings Corrective Plan (1)](https://blog.powereasy.in/tag/unbalanced-currents-warnings-corrective-plan)
- [Under Voltage Warning Corrective Plan (1)](https://blog.powereasy.in/tag/under-voltage-warning-corrective-plan)
- [Voltage Harmonics Warning Corrective Plan (1)](https://blog.powereasy.in/tag/voltage-harmonics-warning-corrective-plan)
- [Voltage Surge Fault Corrective Plan (1)](https://blog.powereasy.in/tag/voltage-surge-fault-corrective-plan)
- [Voltage Unbalance Warning Corrective Plan (1)](https://blog.powereasy.in/tag/voltage-unbalance-warning-corrective-plan)
- [Voltage Variation Warning Corrective Plan (1)](https://blog.powereasy.in/tag/voltage-variation-warning-corrective-plan)
- [WHILE YOU WERE SLEEPING (1)](https://blog.powereasy.in/tag/while-you-were-sleeping)
- [What is Smart Electricity (1)](https://blog.powereasy.in/tag/what-is-smart-electricity)

See all

### Recent Posts

### About Us

**POWEReasy automates electrical safety**

POWEReasy is an IOT enabled device that not only monitors electrical conditions but also identifies all 20 electrical faults. It has the ability to isolate the electrical supply and even diagnose and report issues via the cloud.

### Links

- [About us](https://www.powereasy.in/about-us/#)
- [Product](https://www.powereasy.in/fire-prevention/smart-electrical-auditor-three-phase/)
- [Solution](https://www.powereasy.in/fire-prevention-solutions/)
- [Case Study](https://www.powereasy.in/case-study/)
- [Inquire Now](https://www.powereasy.in/inquire-now/)

### Contact Us

 +919699309799

[info@jhaverilabs.com](mailto:info@jhaverilabs.com)

 Jhaveri Power Labs,  
225, A to Z Industrial Estate, G. K. Marg, Worli   
 Mumbai, Maharashtra 400013

Copyright 2026 | Designed with  by [POWEReasy](http://www.powereassy.in)